EATON 16306-1
Bussmann Series Splicer Blocks
Bussmann series splicer blocks are designed to facilitate the adjustment of wire sizes within a circuit, enabling seamless connections between power sources and branch loads. These blocks are suitable for wire sizes up to 500 kcmil and amp ratings up to 760 A. They are UL Recognized to UL 1059 and approved for use in UL 508A industrial control panels. Available in factory-configured 1- to 4-pole configurations, optional covers can be purchased separately to enhance safety.
Product Attributes
- Brand: Bussmann (Eaton)
- Certifications: UL Recognized to UL 1059 (Guide XCFR2, File E62622), CSA Certified (Class 6228-01, File 15364)
- Flammability Rating: UL 94 V0
Technical Specifications
| Catalog Number Prefix | No. of Poles | Current Rating (A) | Lineside Wire Size (Str/ferrule unless noted)* | Lineside Ports/Pole | Lineside Torque Nm (Lb-in) | Loadside Wire Size (Str/ferrule unless noted)* | Loadside Ports/Pole | Loadside Torque Nm (Lb-in) | SCCR (kA) |
|---|---|---|---|---|---|---|---|---|---|
| 16200-_** | 2, 3, 4 | 175 | 2/0 - #1 Cu/Al (Str) | 1 | 12.4 (110) | 2/0 - #1 Cu/Al (Str) | 1 | 12.4 (110) | 10 |
| 16201-_ | 1, 2, 3 | 150 | 1/0 - #3 Cu (Str) | 1 | 5.6 (50) | 1/0 - #3 Cu (Str) | 1 | 5.6 (50) | 10 |
| 16000-_** | 2, 3, 4 | 175 | #4 - #8 Cu/Al | 2 | 13.6 (120) | #4 - #8 Cu/Al | 2 | 13.6 (120) | 10 |
| 16204-_ | 1, 2, 3 | 200 | #4 - #8 Cu/Al | 2 | 13.6 (120) | #4 - #8 Cu/Al | 2 | 13.6 (120) | 200 |
| 16003-_** | 2, 3, 4 | 255 | 250kcmil - #6 Cu | 1 | 42.4 (375) | 250kcmil - #6 Cu | 1 | 42.4 (375) | 10 |
| 16301-_ | 1, 2, 3 | 255 | 250kcmil - #6 Cu | 1 | 42.4 (375) | 250kcmil - #6 Cu | 1 | 42.4 (375) | 10 |
| 16005-_** | 2, 3, 4 | 310 | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 10 |
| 16303-_ | 1, 2, 3 | 310 | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 10 |
| 16306-_ | 1, 2, 3 | 380 | 500kcmil - 4/0 Cu/Al (Str) | 1 | 56.5 (500) | 500kcmil - 4/0 Cu/Al (Str) | 1 | 56.5 (500) | 10 |
| 16500-_ | 2, 3, 4 | 620 | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 350kcmil - 2/0 Cu/Al (Str) | 1 | 31.1 (275) | 10 |
| 16504-_ | 1, 2, 3 | 760 | 500kcmil - 4/0 Cu/Al (Str) | 1 | 56.5 (500) | 500kcmil - 4/0 Cu/Al (Str) | 1 | 56.5 (500) | 10 |
* 75C wire (higher temperature rated wire acceptable with appropriate derating). Using a ferrule on a stranded conductor requires a correctly sized UL Listed ferrule (customer supplied) applied according to the manufacturers specifications. Ferrule ratings apply to copper wire only.
** Not covered by CSA certification.
See table below for the tested upstream overcurrent protective devices necessary for achieving this SCCR.
Torque rating for dual wire and ferrule application is 30.5 Nm (270 Lb-in).