TE Connectivity 2213600-2
Product Overview
This specification covers the performance, tests, and quality requirements of the "CoolSplice Connector" with part numbers x-2213600-y and 2213800-y, applied according to application specification 114-133061. The CoolSplice Connector is designed for electrical connections and has undergone successful qualification testing.
Brand
TE Connectivity
Product Name
CoolSplice Connector
Certifications
IEC 60998-2-3, UL 486C Listed, UL 1977 Recognized, UL 2459 Listed
Environmental Compliance
RoHS & REACH compliant
| Part Number | Voltage | Current | Temperature | IP Rating |
|---|---|---|---|---|
| x-2213600-y | 600 V ac / dc (UL 486C & IEC60998-2-3) | 12 AWG / 4 mm2: 20 A 14 AWG / 2.5 mm2: 15 A 16 AWG / 1.5 mm2: 15 A 18 AWG / 0.75 mm2: 10 A | -40 C to 105 C (Ambient max 75 C) | IP20 for -4, -5, -6, -9 & 1-2213600-0 IPx5, IPx7 & IPx8 for -1, -2, -3, -7 & -8 |
| 2213800-y | 600 V ac / dc (UL 2459) 450 V ac / dc (IEC 60998-2-3) | 18 AWG / 0.75 mm2: 6.5 A (5 A, IEC) 20 AWG / 0.5 mm2: 6.5 A (5 A, IEC) 22 AWG / 0.35 mm2: 5 A (5 A, IEC) | -40 C to 105 C (Ambient max 75 C) | IP20 for -1 & -3 IPx5, IPx7 & IPx8 for -2 & -4 |
| Test Description | Requirement | Procedure |
|---|---|---|
| Initial examination of product | Meets requirements of product drawing. | Visual, dimensional and functional inspection, according to the Quality Inspection Plan. |
| Visual Examination of Product | The product shall not have visible marks of damage, break, or defect before and after the execution of the tests. | EIA-364-18B |
| Contact resistance | Initial resistance maximum 25 m. Maximum resistance after testing not exceeding 100 m. Open voltage: 20 mV maximum. Current 100 mA maximum. | EIA-364-23, Option 1 |
| Insulation resistance | 500 M minimum. | IEC 60512-3-1 Test 3a |
| Temperature rise | T < 30 C | Measure temperature rise at 1 A and increase current in steps of 1 A. After a stabilization period of 1 hour and up to fail. EIA 364-70, Method 2 |
| Voltage proof (between adjacent contacts and contacts & housing) | 3400 V ac Duration: 60 s. | IEC 60512-4-1, Test 4a UL2459 / UL 486C |
| Cable retention force (axial) | 12 AWG / 4 mm2: 155 N 14 AWG / 2.5 mm2: 120 N 16 AWG / 1.5 mm2: 70 N 18 AWG / 0.75 mm2: 50 N 20 AWG / 0.5 mm2: 50 N 22 AWG / 0.35 mm2: 50 N | No visual damage. EIA 364-13 method A |
| Cable retention force (90) | 12 AWG / 4 mm2: 155 N 14 AWG / 2.5 mm2: 120 N 16 AWG / 1.5 mm2: 70 N 18 AWG / 0.75 mm2: 50 N 20 AWG / 0.5 mm2: 50 N 22 AWG / 0.35 mm2: 50 N | EIA 364-13 method A. Cable pulled 90 on insertion direction (towards the button). No visual damage. |
| Vibration Test | No visual damage. Discontinuity <1 sec. | Duration: 4 hours for each axis (x, y, z). Frequency: 10-200-10 Hz. Peak to peak amplitude 1,0 mm. Speed: 1 octave/min. Acceleration: 5 g. IEC 60068-2-6 |
| Impact | No visual damage. Maximum resistance after testing not exceeding 100 m. | One time dropped from 5 meters on concrete floor. |
| Separation force | Minimum of 50 N. | Pulling two mated CoolSplices apart by means of pulling from wires (see figure 1). Only for 2213600-x. |
| IPX5 | Passing. | IEC 60529 |
| IPX8 (this includes IPx7) | 2 hours submerged in 1 meter depth. | IEC 60529 |
| Cold | -40 C Duration: 2h. | IEC 60068-2-1 |
| Dry heat | 100 C Duration: 2h. | IEC 60068-2-2 |
| Damp heat | 40 2 C Relative humidity: 93 3/-2 % Duration: 4 days. | IEC 60068-2-3 |
| Thermal shock | Ta = -40 C; Tb = 100 C. 100 cycles, 30 min/30 min. | IEC 60068-2-14, Test Na |
| Thermal cycling with current load cyclic | Ta = 20 C (t = 30 min. including transition). Tb = 50 C (t = 30 min. including transition). Number of cycles: 192. Temperature transition rate: 5 C/min. Total cycle duration: 1 h. Current: 1,5 A for 45 min/0 A for 15 min. | IEC 60068-2-14, test Nb IEC 60512-9-5 Test 9e |
| Test Group | Test Sequence (b) |
|---|---|
| A (2213600-x) | Visual examination of product: 1, 13 Contact resistance: 2, 4, 6, 8, 10, 12 Insulation resistance: 3, 13 Temperature rise: 5, 15 Voltage Proof: 11 Cable retention force (axial): 9 Cable retention force (90): 6 Vibration Test: 5 Impact: 5 Separation force: 7 IPX5: 3, 7 IPX8 (this includes IPX7): 9 Cold: 7 Dry heat: 9 Damp heat: 11 Thermal shock: 3 Thermal cycling with current load cyclic: 3 |
| B (2213800-x) | Visual examination of product: 1, 17 Contact resistance: 2, 6, 8, 10, 12, 16 Insulation resistance: 4, 14 Temperature rise: 5, 15 Voltage Proof: 11 Cable retention force (axial): 9 Cable retention force (90): 6 Vibration Test: 5 Impact: 5 Separation force: N/A IPX5: 3, 7 IPX8 (this includes IPX7): 9 Cold: 7 Dry heat: 9 Damp heat: 11 Thermal shock: 3 Thermal cycling with current load cyclic: 3 |
| C (2213600-x) | Visual examination of product: 1, 10 Contact resistance: 2, 4, 6, 8 Insulation resistance: N/A Temperature rise: N/A Voltage Proof: N/A Cable retention force (axial): N/A Cable retention force (90): N/A Vibration Test: N/A Impact: N/A Separation force: N/A IPX5: N/A IPX8 (this includes IPX7): N/A Cold: N/A Dry heat: N/A Damp heat: N/A Thermal shock: N/A Thermal cycling with current load cyclic: N/A |
| D (2213800-x) | Visual examination of product: 1, 8 Contact resistance: 2, 4, 6 Insulation resistance: N/A Temperature rise: N/A Voltage Proof: N/A Cable retention force (axial): N/A Cable retention force (90): N/A Vibration Test: N/A Impact: N/A Separation force: N/A IPX5: N/A IPX8 (this includes IPX7): N/A Cold: N/A Dry heat: N/A Damp heat: N/A Thermal shock: N/A Thermal cycling with current load cyclic: N/A |
| (2213600-x) | Visual examination of product: 1, 5, 7 Contact resistance: 2, 4 Insulation resistance: N/A Temperature rise: N/A Voltage Proof: N/A Cable retention force (axial): N/A Cable retention force (90): N/A Vibration Test: N/A Impact: N/A Separation force: N/A IPX5: N/A IPX8 (this includes IPX7): N/A Cold: N/A Dry heat: N/A Damp heat: N/A Thermal shock: N/A Thermal cycling with current load cyclic: N/A |
| (2213800-x) | Visual examination of product: 1, 5, 7 Contact resistance: 2, 4 Insulation resistance: N/A Temperature rise: N/A Voltage Proof: N/A Cable retention force (axial): N/A Cable retention force (90): N/A Vibration Test: N/A Impact: N/A Separation force: N/A IPX5: N/A IPX8 (this includes IPX7): N/A Cold: N/A Dry heat: N/A Damp heat: N/A Thermal shock: N/A Thermal cycling with current load cyclic: N/A |