TE Connectivity 2213600-8
CoolSplice Connector
The CoolSplice Connector, with part numbers x-2213600-y and 2213800-y, is designed for electrical connections. This specification outlines the performance, testing, and quality requirements for these connectors, applied according to application specification 114-133061. The product is suitable for various wire gauges and electrical ratings, with specific models offering different IP ratings for environmental protection.
Product Attributes
- Brand: TE Connectivity
- Trademarks: TE Connectivity, TE connectivity (logo), TE (logo)
- Compliance: RoHS & REACH compliant
Technical Specifications
| Part Number | Wire Gauge Suitability | Voltage | Current | Temperature Range | IP Rating | Industry Standards |
| x-2213600-y | 12 AWG/14 AWG to 14 AWG/16 AWG (approx. 4 mm/2.5 mm to 2.5 mm/1.5 mm) | 600 V ac / dc (UL 486C & IEC60998-2-3) | 12 AWG/4 mm: 20 A; 14 AWG/2.5 mm: 15 A; 16 AWG/1.5 mm: 15 A; 18 AWG/0.75 mm: 10 A | -40 C to 105 C (Ambient max 75 C) | IP20 (for -4, -5, -6, -9, 1-2213600-0); IPx5, IPx7 & IPx8 (for -1, -2, -3, -7, -8) | UL 486C Listed; IEC 60998-2-3 |
| 2213800-y | 18 AWG (approx. 0.75 mm); 20 AWG /22 AWG (approx. 0.5 mm / 0.34 mm) | 600 V ac / dc (UL 2459); 450 V ac / dc (IEC 60998-2-3) | 18 AWG/0.75 mm: 6.5 A (5 A IEC); 20 AWG/0.5 mm: 6.5 A (5 A IEC); 22 AWG/0.35 mm: 5 A (5 A IEC) | -40 C to 105 C (Ambient max 75 C) | IP20 (for -1, -3); IPx5, IPx7 & IPx8 (for -2, -4) | UL 1977 Recognized; UL 2459 Listed; IEC 60998-2-3 |
Test Requirements Summary
| Test Description | Requirement | Procedure |
| Initial examination of product | Meets requirements of product drawing. | Visual, dimensional and functional inspection, according to the Quality Inspection Plan. |
| Visual Examination of Product | No visible marks of damage, break, or defect. | Before and after the execution of the tests. |
| Electrical Contact resistance | Initial max 25 m. After testing max 100 m. | Open voltage: 20 mV max; Current: 100 mA max; EIA-364-23, Option 1 |
| Insulation resistance | 500 M minimum | IEC 60512-3-1 Test 3a |
| Temperature rise | T < 30 C | Measure at 1 A and increase in steps of 1 A. EIA 364-70, Method 2 |
| Voltage proof (between contacts and contacts & housing) | 3400 V ac | Duration: 60 s; IEC 60512-4-1, Test 4a |
| Mechanical Cable retention force (axial) | See table below | No visual damage. EIA 364-13 method A |
| Mechanical Cable retention force (90) | See table below | EIA 364-13 method A. |
| Vibration Test | No visual damage. Discontinuity <1 sec | Duration: 4 hours/axis; Frequency: 10-200-10 Hz; Amplitude: 1.0 mm; IEC 60068-2-6 |
| Impact | No visual damage. Max resistance after testing not exceeding 100 m. | Dropped from 5 meters on concrete floor. |
| Separation force (for 2213600-x) | Minimum of 50 N | Pulling two mated CoolSplices apart by means of pulling from wires. |
| Environmental IPX5 | Passing | IEC 60529 |
| Environmental IPX8 (includes IPx7) | 2 hours submerged in 1 meter depth | IEC 60529 |
| Environmental Cold | -40 C, 2h | IEC 60068-2-1 |
| Environmental Dry heat | 100 C, 2h | IEC 60068-2-2 |
| Environmental Damp heat | 40 2 C, 93 3/-2 % RH, 4 days | IEC 60068-2-3 |
| Environmental Thermal shock | Ta = -40 C; Tb = 100 C, 100 cycles (30 min/30 min) | IEC 60068-2-14, Test Na |
| Environmental Thermal cycling with current load cyclic | Ta = 20 C (30 min); Tb = 50 C (30 min); 192 cycles | Current: 1.5 A for 45 min/0 A for 15 min. IEC 60068-2-14, test Nb |
Cable Retention Force Minimums:
- 12 AWG / 4 mm: 155 N
- 14 AWG / 2.5 mm: 120 N
- 16 AWG / 1.5 mm: 70 N
- 18 AWG / 0.75 mm: 50 N
- 20 AWG / 0.5 mm: 50 N
- 22 AWG / 0.35 mm: 50 N